Raritan PX4-5256CR.
Inlet metered + outlet Metered + switched Power Distribution Unit, IEC C20 100-240V Inlet, 3.8 kvA, Horizontal input, 12 outlets: 8x C13, 4x combined C13/C19 outlets,
Billing-Grade (± 0.5%) Energy and Power Quality Metering [kW, kVA, V, A, Voltage and Current Harmonic Distortion, True and Displacement Power Factor, Voltage Dip and Voltage Swell, Neutral Current and Voltage, Current Inrush, and Crest Factor]. Remote network monitoring via HTML, JSON-RPC, Redfish API, SSH, Telnet, MODBUS/TCP, and SNMPv3.
Hot-swappable Controller with onboard embedded processor with minimum 536MHz clock speed, 16MB SPI Flash, and 64MB DDR2 RAM.
Physically cascade 32 PDUs under one Ethernet port or 16 PDUs with USB. Linking (Shared GUI) of up to 8 PDUs. Environmental monitoring [temp/humidity] capable – up to 32 sensor functions or 12 sensor packages.
Individual outlet numbers labeled on chassis.
Automated deployment via TFTP, DHCP, SSH(CLI), or USB Flash Drives. Data logging via HTTP/S or MQTT. Wi-Fi Capable. USB Webcam Capable. iOS or Android App. Dual 10/100/1000 Ethernet port.
Mechanical locking function for Outlets. 16A Breakers, 10kAIC. Breaker metering and alarming (0V detection).
Maximum ambient temperature 60°C at full load.
Attested passed VAPT (Vulnerability Assessment and Penetration Testing), IPv6 Ready, ISO 27001 compliant.
Features
Energy Metering Voltage (V), Current (A), Active Power (kW), Real Power (kVA), Energy (kWh), Power Factor
Metering Accuracy Class 0.5 meter
Metering per input line Yes
Metering per Branch Circuit Breaker Yes
Metering per Output Receptacle Yes
Remote Outlet Switching Yes
Power Quality Monitoring Voltage and Current Harmonic Distortion; Distortion Power Factor; Voltage Dip and Voltage Swell; Neutral Current, Current Inrush, Crest Factor
Outlet Power Distribution Alternating Branch
Replaceable Controller Yes, hot-swappable
Environmental Sensor Ready Yes
Compatible Sensors Temperature, Humidity, Air Flow, Differential Pressure, Dust/Particle, Water Leak, Proximity/Motion, Vibration, Dry Contact, and Contact Closure.
View all sensors.
PDU Linking Link up to 8 PDUs where the Primary PDU has knowledge and power information from the attached Expansion PDUs. Redundant power from the first expansion unit ensures uptime even if the Primary PDU loses power.
Cascading Physically cascade 32 PDUs under one ethernet port or 16 PDUs with USB using bridging mode, or additionally, save IP addresses using a single IP address with port forwarding.
Linking Yes, a maximum of 8 PDUs can be linked using the PDU Link Port; PDU 1 is defined as the Primary PDU and can link up to 7 additional PDUs, called Link PDUs, totaling 8 PDUs.
Networking (10/100/1000 Base T) Ethernet, Secondary redundant (10/100/1000 Base T) Ethernet. Optional WiFi (802.11 a/b/g/n).
Remote Management HTTP(s); SSH (CLI); Telnet; RS-232 (Serial); SNMP version v2/v3; SMTP; JSON-RPC API; MODBUS-TCP; Redfish API
Onboard Display Color, matrix LCD display : Voltage, current, or active power (per line, per breaker, or per receptacle / outlet); Alarms; Configuration information (name, ratings, IP / Networking information). Auto-flip orientation.